Page 72 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
P816 Echo Time Raw
The time (in ms) from the transmit pulse to the processed echo.
Profile Pointer (P817 to P825)
When one of these parameters is accessed, the scope display changes: The Echo Lock
Window becomes the Profile Pointer. The Profile Pointer may be moved to any point on
the Echo Profile to gain specific information about the profile according to the selected
parameter.
To move the Profile Pointer to a specific point, enter the desired value and it will move to
the nearest acceptable Echo Profile point.
Alternatively, to scroll the Profile Pointer along the Echo Profile:
1. Press to display the Auxiliary Function symbol.
2. Press or to move the Profile Pointer to the left or right respectively.
3. When the Profile Pointer Parameters are exited and RUN mode is entered, the
scope display automatically changes back to include the Echo Lock Window.
P817 Profile Pointer Time
The time (in ms) from the transmit pulse to the Profile Pointer.
P818 Profile Pointer Distance
The distance between the transducer face and the Profile Pointer.
Values Range: 0.0 to 9999 (view only)
Values Range: 0.000 to 9999 (view only)
Related
• P818 Profile Pointer Distance
• P819 Profile Pointer Amplitude
• P820 Algorithm
• P821 Spike Filter
• P822 Narrow Echo Filter
• P823 Reform Echo
• P825 Echo Marker Trigger
Values Range: 0.000 to 9999 (view only)
Related
• P817 Profile Pointer Time
• P819 Profile Pointer Amplitude
• P820 Algorithm
• P821 Spike Filter
• P822 Narrow Echo Filter
• P823 Reform Echo
• P825 Echo Marker Trigger